Ravel RE - 104 Spécifications Page 13

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 24
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 12
Man-1078_Sigma_CP_22
Page 13 of 24
10B11. Aux 24V DC supply
An auxiliary 24V DC supply is provided to enable local signalling or control of ancillary systems such as door
release controllers.
The terminals for the Aux 24V supply are labelled Aux 24V and ROV. The ROV terminal is the negative
terminal and is the same terminal that should be used to switch the remote control terminals.
It is possible to make the ROV terminal pulsing so that by connecting it to the AL terminal via a remote, volt
free contact, it can be used to pulse the dedicated sounder circuits in response to a signal from another
system for example to give an alert. See programming code 24.
The supply is fitted with an electronic self resetting fuse to protect the control panel’s 24V supply in the
event of a wiring fault.
Any standing load on the Aux 24V supply must be taken into account when calculating battery standby times
as standby time will be significantly affected by even modest standing loads. It is recommended that the
Aux24V output is not used to power standing loads and not used to supply loads of greater than 300
milliamps
Where the Aux 24V supply is used to power electromechanical devices such as relays or door retainers it is
imperative that a suppression diode is fitted across the coil of the electromechanical device to prevent the
generation of high voltage transients back to the control panels power supply.
The Aux 24V DC Supply is not suitable for powering Sigma CP sounder boards, a separate power supply
should be used for these.
11B12. Connection to relay contacts
Volt free changeover relay contacts are provided for local control and signalling if required. These contacts
are rated for switching signalling circuits only and the maximum ratings listed in table 1 on page 5 should
not be exceeded under any circumstances.
Fault relay
The fault relay is normally energised and will de-energise upon any fault condition including total loss of power.
Local fire relay
The local fire relay will energise upon activation of a fire condition on any of the zones or pressing of the
sound alarm button on the front panel. The relay will remain activated until the alarm is silenced or the
panel is reset. This relay will not operate upon activation of the remote AL input or when a fire condition is
triggered on a zone that is in test mode.
Fire relay
The fire relay will energise upon activation of a fire condition on any of the zones. The relay will remain
activated until the control panel is reset. This relay will
NOT
operate upon activation of the remote AL input.
Individual zones can be configured not to operate the Fire relay by setting configuration options E1 to E8.
12B13. Connection to Repeater panels
Repeater panels connect via a 2 core cable to the terminals marked RS485 + and on the Sigma CP main
control panel PCB. Up to 7 repeaters may be connected and each repeater has terminals for the incoming
cables and outgoing cables. All except the last ancillary board, sounder board or repeater panel connected to
the cable must have the jumper links J2 removed.
Set the repeater address using the DIP switch (SW7); ensure no two repeaters share the same address.
Apply power to main panel first and then all repeater panels. Turn on the Enable Control keyswitch and set
the Write Enable switch to on then briefly press the PROCESSOR RESET button on the main panel. Wait for a
few seconds and the main panel will show the addresses of the repeaters that were found on the display for
instance r1 indicates that a repeater at address 1 has been found.
Turn the write enable switch of, then on again and then press the ENTER button to accept each repeater
that has been found. When all repeaters have been added, set the main panel Write Enable switch to off.
Press the Watchdog reset switch on the main panel.
All repeaters are now configured and the main control panel will report a fault if any repeaters that have
been accepted become faulty or go off line.
For full details of commissioning procedures for repeaters see the Sigma CP Repeater Operation and
maintenance manual.
Please note that repeaters can only be fitted to panels containing boards labeled
S4XXA or above. They will not work with panels containing boards without an alpha
suffix.
Vue de la page 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 23 24

Commentaires sur ces manuels

Pas de commentaire