Ravel RE - 104 Spécifications Page 19

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 33
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 18
P/N RE - 102 / 104 Rev. No. 0
18
MENU Key: The MENU key is used to enter into the programming
mode for changing the zone status and other settings. The various
steps involved in this menu are shown as flow chart 4.3.5. After
entering into the menu, screen will be as below,
4.2 Status LED:
Normal: In the Normal Condition,
SYSTEM ON, AC POWER ON, green LED will
be illuminated. There should be no other amber / red LED visual
indication or audible tone.
A.C POWER ON: This LED indicates the presence of main supply.
Whenever the Main Supply (220v A.C) is present this LED will glow.
Whenever the Main Supply (220v A.C) fails / fuse blown, the AC Power
on LED will OFF and it also indicated by fault Buzzer tone.
BATTERY ON: This LED indicates the presence of standby power supply.
Whenever the Main Supply (220v A.C) fails, the panel supply is
switched to standby power supply with BATTERY ON indication.
Whenever the backup battery fails / fuse blown, the battery fail is
indicated by LCD with fault Buzzer tone.
Note:
Whenever the backup battery voltage goes below the 21v, the
battery on LED will be blinking with toggle Buzzer tone.
HOOTER FAULT: Whenever there is any fault in Notification Appliances
Circuits like Hooter (Sounder) loop open / short, it will be identified by
COMMON HOOTER FAULT LED.
SILENCED: Whenever the External Sounders are silence in presence of
actual fire. After silencing this LED glows with toggle buzzer tone.
1. Zone 1
Enable