P/N RE - 102 / 104 Rev. No. 0
22
This feature helps to perform the testing of devices
by a single person. In this mode if the zone detects any
fire then after 4 seconds the panel will get automatically
silenced. After 2 seconds of silence, the zone will go to
reset.
Note1:
a. If there is no more testing, please ensure that the
zone is brought back to the normal Condition.
b. To bring back the zone loop to normal condition,
same procedure is followed as for the test.
c. If the zone is kept in Walk test mode for 10 minutes
with out any test the panel comes out of the walk
test mode automatically.
d. During test condition that the other zones that are
not in test mode fire will consider as actual fire.
4.3.5.2. Zone 2
From this menu, the zone 2 loop can configured as
enable, disable, Zone test and Walk test. The default
option is ‘Enable’. To change the options press ‘Enter’ key,
then change the options by using the left/ right cursor
keys. The Screen will be as shown below.
4.3.5.3. Zone 3
From this menu, the zone 3 loop can configured as
enable, disable, Zone test and Walk test. The default
option is ‘Enable’. To change the options press ‘Enter’ key,
then change the options by using the left/ right cursor
keys. The Screen will be as shown below.
2. Zone 2
<Enabled>
3. Zone 3
<Enabled>